EasyManua.ls Logo

Gree GRS-CQ8.0Pd/NaEK - Outline Dimensions; Outline Dimensions of Outdoor Unit

Gree GRS-CQ8.0Pd/NaEK
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product
11
14(57.2)
1.442
1.402
1.350
1.302
1.252
15(59.0)
1.490
1.450
1.400
1.350
1.302
18(64.4)
1.539
1.502
1.451
1.402
1.350
Computer of actual cooling capacity: actual cooling capacity = nominal cooling capacity x cooling
capacity correction coefficient.
Heating Capacity Correction
GRS-CQ8.0Pd/NaE-K,GRS-CQ10Pd/NaE-K,GRS-CQ12Pd/NaE-K,GRS-CQ14Pd/NaE-K,
GRS-CQ16Pd/NaE-K,GRS-CQ12Pd/NaE-M,GRS-CQ14Pd/NaE-M,GRS-CQ16Pd/NaE-M.
Performance Correction
Outflow
Heated
Water
(
)
Ambient Temperature
(
)
-15(5)
-10(14)
-5(23)
0(32)
5(41.0)
10(50)
15(59.0)
20(68.0)
25(77.4)
30(86)
0.81
0.91
1.00
1.10
1.18
1.26
1.35
1.41
1.45
35(95)
0.74
0.84
0.93
1.03
1.11
1.19
1.28
1.36
1.41
40(104)
0.67
0.77
0.87
0.96
1.04
1.12
1.20
1.25
1.31
45(113)
0.60
0.70
0.80
0.89
0.97
1.05
1.13
1.19
1.25
50(122)
0.53
0.63
0.73
0.82
0.90
0.98
1.06
1.11
1.18
55(131)
0.46
0.56
0.66
0.74
0.83
0.90
0.98
1.05
1.10
Computer of actual heating capacity: actual heating capacity = nominal heating capacity x heating
capacity correction coefficient.
2 Outline Dimensions
2.1 Outline dimensions of outdoor unit
GRS-CQ8.0Pd/NaE-K(O), GRS-CQ10Pd/NaE-K(O)

Table of Contents