Unit Control
67
changed freely. Under the cooling mode, when it is set to “With”, the leaving water temperature
range is 18-25 and the default is 18 ; when it is set to “Without”, the range is 7-25 , the
default is 7 .
“Floor config” can be changed only when the unit is turned off.
2.2.29 Remote Sensor
It can be configured to be “
With
” or “
Without
” based on the actual condition.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Remote sensor
”, then, configure it through the
Up/Down
key , “
With
” or “
Without
”.
[Notes]
It will be memorized upon power failure.
T-room ctrl” can be selected only when the Remote Sensor is set to “With”.
3.2.2.30 Air removal
This function is intended to expel air inside the water system with only the water pump in operation
when installation of the unit is finished.
[Operation Instructions
]
Go to the
FUNCTION
page and locate
Air removal
”, then, configure it through the
Up/Down
key
, “
On
” or “
Off
”.
[Notes]
It will not be memorized upon power failure.
It can be set only when the unit is turned off.
3.2.2.31 Address
It is used to identify the unit in use in the central control system.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Address
”, then, configure it through the
Up/Down
key
to set the address.
[Notes]
It indicates the address of the control and is intended for the group control.
It will not be memorized upon power failure.
The address range is [1,125] and [127,253]
The default address is 1 for the initial use.
3.2.2.31 Gate-Controller
(Gate-Ctrl.)
It can be configured to be “
On
” or “
Off
” based on the actual condition.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Gate-Controller
”, then, configure it through the Up/Down
key , “
On
” or “
Off
”.
[Notes]
When it is activated, the control will check the card is inserted or not. If inserted, the control will
run normally; if not, the control will turn off the unit and back to the homepage. In this case, any
key operation is ineffective (except for the combined key operation), or a dialogue box will pop
up, warning"Keycard uninserted!".
It will not be memorized upon power failure.