Unit Control
70
Weather-dependent
Mode for heating
temp.]
[Normal temp.]
the Weather-dependent
Mode setting changes.
16
Lower limit ambient
temperature at the
Weather-dependent
Mode for cooling
Lower AT-Cool
8~25°C
46~77°F
25°C/77°F
17
Upper limit
temperature at the
Weather-dependent
Mode for cooling
Upper AT-Cool
26~50°C
79~122°F
40°C/104°F
18
Upper limit room
temperature at the
Weather-dependent
Mode for cooling
Upper
RT-Cool
24~30°C
75~86°F
27°C/81°F
19
Lower limit room
temperature at the
Weather-dependent
Mode for cooling
Lower
RT-Cool
18~23°C
64~73°F
22°C/72°F
20
Upper limit
water-out
temperature at the
Weather-dependent
Mode for cooling
Upper
WT-Cool
15~25°C[Without
Floor]
22~25°C[With Floor]
59~77°F
[Without Floor]
72~77°F
[With Floor]
15°C/59°F[Without Floor]
23°C/73°F[With Floor]
21
Lower limit
water-out
temperature at the
weather-dependent
mode for cooling
Lower
WT-Cool
7~14°C[Without
Floor]
18~21°C[With Floor]
45~57°F[Without
Floor]
64~70°F[With Floor]
7°C/45°F[Without Floor]
18°C/64°F[With Floor]
22
Temperature
deviation for cooling
ΔT-Cool
2~10°C
36~50°F
5°C/41°F
23
Temperature
deviation for
heating
ΔT-Heat
2~10°C
36~50°F
10°C/50°F
24
Temperature
deviation for
heating water
ΔT-hot water
2~8°C
36~46°F
5°C/41°F
25
Room temp
variation
ΔT-Room
temp
1~5°C
36~41°F
2°C/36°F
26
Run time
Run time
1~10min
/
/
27
Solar kit-start temp
variation
T-Solar start
10~30°C
50~86°F
15°C/59°F
28
Reserved
Reserved
Reserved
Reserved
Reserved