Wired Controler XK60
62
automatically.
Notes:
①
If the unit is not connected with the ambient temperature sensor, after 12h
electrification, the display of the ambient temperature sensor will be
shielded.
②
If the outdoor temperature sensor has error, after 12h electrification, the
display of the ambient temperature sensor will be shielded.
3.20.5 Indoor fan shutdown mode setting
Under unit OFF status, simultaneously press “Function” and “Timer”
button for 5s, the wired controller will enter parameter setting interface.
Press “Mode” button to set till “05” is shown on the temperature displayed
area. Then the unit will enter the indoor fan shutdown mode.
Two options are available for the indoor fan shutdown mode:
Mode 1: When the temperature reaches certain value, the indoor fan
will not be shut down at any mode except heating mode. After the unit is
shut down, for the duct type unit and the floor ceiling type unit, the indoor
fan will blow the extra heat for 60s and then stop running. For the
cassette type unit, its indoor fan will operate at low fan speed and blow
the extra heat for 60s only when error happens to it.