Wired Controler XK60
18
Timer On setting starts when the unit under the ON state is turned off;
Timer Off setting starts when the unit under the OFF state is turned on.
3.8 Air Exchange Setting (only for units with "Fresh Air damper)
How to activate the air exchange function:
Under the ON state of the unit, press the Function button to select
the “AIR” function, with the function symbol flashing, and then press or
to adjust the “AIR” type, after that, press the Enter/Cancel button to
activate this function. When this function is activated, the symbol will be
displayed. Type 1 is the defaulted “AIR” type.
There are 10 “AIR” function types , but only 1-2 types are for the
wireless remote controller.
1――The unit continuously runs for 60min, and fresh air damper
runs for 6 min.
2――The unit continuously runs for 60min, and fresh air damper
runs for 12 min.
3――The unit continuously runs for 60min, and fresh air damper
runs for 18 min.
4――The unit continuously runs for 60min, and fresh air damper runs