555C Electric Bender Classic
Offset Table
X Table
OFFSET ➤ 246810
Max Conduit Size 3/4 1-1/2 2 2
Center-to-Center 7-3/4 15-7/16 23-3/16 30-15/16 38-5/8
Max Conduit Size 3/4 1 1-1/2 2
Center-to-Center 8 12 16 20
Max Conduit Size 1/2 1 1-1/4
Center-to-Center 8-1/2 11-5/16 14-1/8
15°
30°
45°
OFFSET ➤ 12 14 16 18 20 22
Max Conduit Size 2
Center-to-Center 46-3/8 54-1/16 61-13/16 69-9/16 77-1/4 85
Max Conduit Size 2
Center-to-Center 24 28 32 36 40 44
Max Conduit Size 1-1/2 2 2
Center-to-Center 16-15/16 19-13/16 22-5/8 25-7/16 28-1/4 31-1/8
15°
30°
45°
CENTER-TO-CENTER DISTANCE = OFFSET HEIGHT x MULTIPLIER
OFFSET ANGLE 10° 15° 22-1/2° 30° 45°
MULTIPLIER 5.8 3.9 2.6 2.0 1.4
Figures are approximate
CONDUIT SIZE 1/2 3/4 1 1-1/4 1-1/2 2
“X” 3-1/16 3-1/16 3-3/16 4 4-1/4 4-1/2
Figures are approximate
Bending Instructions (cont’d)
Offsets
1. Measure the height and length of the obstruction.
Select the angle to be used.
2. See the Offset Table. The height of the obstruction
must be equal to or greater than the minimum offset.
3. Refer to the X Table to find the X dimension. Refer
to the Offset Table to find the center-to-center
distance.
Note: If the center-to-center distance is not shown,
calculate it by using the multipliers shown in the
Offset Table.
4. Mark the conduit as shown.
5. Insert the conduit into the bender. Align Mark 1 with
the front edge of the hook and bend the conduit.
6. Align Mark 2 with the front edge of the hook. Without
removing the conduit from the bender, rotate the
conduit 180°. Make the second bend.
LENGTH
HEIGHT
LENGTH
MARK 1
MARK 2
CENTER TO CENTER
DISTANCE
X
OBSTRUCTION