Model
Specifications
MID
30KTL3-X
MID
33 KTL3-X
MID
36 KTL3-X
MID
40KTL3-X
Input data(DC)
Max. recommended PV
power(for module STC)
45000W
49500W
54000W
60000W
Max. DC voltage
1100V
Start voltage
250V
Nominal voltage
600V
MPP voltage range
200-1 000V
No. of MPP trackers
3
4
No. of PV strings per MPP
trackers
2/2/2
2/2/2
2/2/2/2
2/2/2/2
Max. input current per MPP
trackers
26A*3
26A*3
26A*4
26A*4
Max. short-circuit current per
MPP trackers
32A*3
32A*3
32A*4
32A*4
Backfeed current to PV array
0A
Output data(AC)
AC nominal power
30000W
33000W
36000W
40000W
Max. AC apparent
33000VA
36300VA
39600VA
44000VA
Nominal AC voltage/range
230/400V
340-440V
AC grid frequency/range
50/60 Hz
45~55Hz/55-65 Hz
Max. output current
50.5A
55.5A
60.0A
66.6A
AC inrush current
60A
Max. output fault current
106.1A
106.1A
124.8A
124.8A
Max. output overcurrent Pro-
tection
106.1A
106.1A
124.8A
124.8A
Power factor(@nominal
power)
>0.99
Adjustable power factor
0.8Leading ...0.8Lagging
THDi
<3%
AC grid connection type
3W+PE /3W+N + PE
Efficiency
Max. efficiency
98.8%
Euro-eta
98.5%