6.2 Wiring AC Output
You must install a separate single-phase circuit-breaker or other load
disconnection unit for each inverter in order to ensure that the inverter
can be safely disconnected under load.
NOTE :The inverter has the function of detecting residual current and
protecting the inverter against residual current. If your inverter has to equip
a AC breaker which has the function of detecting residual current ,you must
choose a AC breaker with the rating residual current more than 300mA.
You must install a separate single-phase circuit-breaker or other load disconnection
unit for each inverter in order to ensure that the inverter can be safely disconnected
under load.
We suggest you choice the AC breaker rating current in this table:
The AC wiring step:
1. Uninstall the parts of the AC connection plug from the accessory bag.
2. Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in
sequence, insert cables into connection terminal according to polarities indicates on it and
tighten the screws firmly. Please try to pull out the wire to make sure the it’s well connected.