EasyManua.ls Logo

Growatt MIN 2500TL-XH - Inverter Demand Response Modes-Power Control Interface(PCI) for EU

Growatt MIN 2500TL-XH
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
DRM 3
3
8
Do not consume at more than 75% of rated power
DRM 4
4
8
Increase power consumption
DRM 5
1
7
Do not generate power
DRM 6
2
7
Do not generate at more than 50% of rated power
DRM 7
3
7
Do not generate at more than 75% of rated power
DRM 8
4
7
Increase power generation (subject to constraints from
other active DRMs)
6.9.2 Inverter demand response modes-Power Control
Interface(PCI) for EU
This series inverter has the function of demand response modes, We use 8Pin COM
PORT as Power Control Interface(PCI) for European models.
WARNING
Excessive voltage can damage the inverter!
External voltage of PCI PORT dont over +5V.
1 2 3 4 5 6 7 8
RRCR
PCI Connector
K1
K2
K3
K4
6.9.2.1 The connector pin assignment and function definition
Pin
Description
Connect to RRCR
1
+12V
Not connected
2
GND
3
Not connected
Not connected

Table of Contents