EasyManuals Logo

Growatt ShineSEM-X User Manual

Growatt ShineSEM-X
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
17
18
Log in to the built-in page, the login account is "admin", the password is "admin", select
"Device Monitoring" in the first-level menu, select "Inverter" in the second-level menu,
and select "Device Maintenance" in the third-level menu.
(1) Select the device to be added, "inverter", "electric meter", "environmental monitor"
and "PID device". Here is an example of adding an inverter:
Figure 3-9 Inverter window
( 2) Click "Add", and the "Add Data" window will pop up.
Figure 3- 10 Add data window
(3) 485 channel where the device is located in the drop-down list of "Channel" , there
are four channels of RS 485-1 , RS485-2 , RS485-3 and RS485-4 .
Figure 3- 11 Channel selection
(4) Select the device type in the drop-down list of "Type".
Figure 3- 12 Device type selection
(5) "Start address" writes the start address of the added device, for example: suppose the
address of the photovoltaic inverter to be monitored is "1", then the start address is 1 .
Note: Only 32 devices can be added to each RS 485 channel , and the address of the
photovoltaic device is 0-254 ;
Figure 3- 13 Start address filling
(6) Number of addresses: ShineMaster supports adding multiple devices of the same type
with consecutive addresses at one time. For example: Suppose there are four
photovoltaic inverter addresses to be monitored, and the addresses are 1, 2, 3, and 4
respectively, then write "1" for "start address" and "4" for "number of addresses".
Note: There are only 32 devices that can be added to each RS 485 channel . Assuming
that starting from address 1, only 32 devices can be added continuously at a time;
Figure 3- 14 Add the number of addresses
(7) Then click Submit. After the prompt is successful, select "System Information" in the
first-level menu, and select "Device List" in the second-level menu to check whether the
inverter is added successfully.
Figure 3- 15 Add success prompt