Wake-up Delay
Time
of Dry-Water
Dry out recovery time, under auto dry run mode or
water sensor mode
Automatic Dry run
protection
0.0%:No automatic dry run protection
0.1%~100.0%:It is determined by P15.15
100% corresponds to the rated motor current.
If the running frequency >30Hz,and the current
corresponding to the current frequency is less than
P15.15, after the time set by P15.13, the inverter
will stop run,otherwise,it will operate normally.
After the time set by P15.14, the inverter will reset.
Delay Time setting of Full-water, under water
sensor mode
Reset Delay of
Full-Water
Dry out recovery time, under water sensor mode
If the output frequency is less than the frequency
of Weak Light, it will stop run.
Delay Time of weak light, after the time set by
P15.20, the inverter will stop run.
Reset Delay of
Weak Light
Reset Delay of weak light,after the time set by
P15.21, the inverter will reset
Troubleshooting
The inverter has complete protection. When a failure occurs, the inverter will take protective measures. The
general protection is to stop the motor from running and forbid it to restart within a certain period.
Inc OVP
Dec OVP
Const OVP
1.
Input voltage is too high
2.
There is large energy feedback
1.Check the voltage of solar
array
2.Check if the DEC time of the
load is too short or the inverter
starts during the rotation of the
motor
1.Input voltage is too low;
2.Illumination intensity is too weak
Check the voltage of solar array