two analog inputs
two digital inputs or one digital input and one open-collector
output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
See fig. Connection terminals, optional for CRE, CRIE, CRNE,
CRKE, SPKE, MTRE and CME pumps.
Digital input 1 is factory-set to be start-stop input where
open circuit results in stop. A jumper has been factory-
fitted between terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external start-stop or any
other external function.
DANGER
Electric shock
Death or serious personal injury
Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire lengths.
Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV), thus ensuring protection
against electric shock.
Start-stop: (Digital input 1) = Terminals 2 and 6
Pressure sensor: (Analog input 1) = Terminals 4 and 8
Pressure switch: (Digital input 3) = Terminals 6 and 10
External analog signal input: (Analog input 2) = Terminals 7 and
23
GENIbus Terminals A, Y and B
Signal relay outputs
- Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC to the
output.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
- Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE).
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
TM053510
* If you use an external supply source, there must be a connection
to GND.
Connection terminals, optional for CRE, CRIE, CRNE, CRKE,
SPKE, MTRE and CME pumps
Terminal Type Function
NC
Normally closed
contact
Signal relay 1
(LIVE or PELV)
C1 Common
NO
Normally open
contact
NC
Normally closed
contact
Signal relay 2
(PELV only)
C2 Common
NO
Normally open
contact
10 DI3/OC1
Digital input/output,
configurable.
Open collector: Max. 24 V
resistive or inductive.
4 AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5 +5 V
Supply to potentiometer and
sensor
6 GND Ground
A GENIbus, A GENIbus, A (+)
17
English (US)

Table of Contents

Other manuals for Grundfos CRE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CRE and is the answer not in the manual?

Grundfos CRE Specifications

General IconGeneral
Protection ClassIP55
MaterialStainless Steel
ApplicationsWater supply, pressure boosting, irrigation
Impeller MaterialStainless Steel
Pump Housing MaterialStainless Steel
Connection SizeDN32 to DN200 (depending on model)
Power Supply3-phase
ControlIntegrated frequency converter

Related product manuals