11.2 Back to factory settings
Follow this procedure to get back to the factory settings:
1. Switch off the power supply to the CUE.
2. Press [On/Off], [OK] and [+] while switching on the power
supply.
The CUE will reset all parameters to factory settings. The display
will turn on when the reset is completed.
11.3 Start-up guide
Use the start-up guide for the general setting of the CUE
including the setting of the correct direction of rotation.
The start-up guide is started the first time when the CUE is
connected to the power supply. It can be restarted in the
"GENERAL" menu. Please note that in this case all previous
settings will be erased.
Bulleted lists show possible settings. Factory settings are shown
in bold.
11.3.1 Welcoming display
• Press [OK]. You will now be guided through the start-up guide.
11.3.2 Language (1/16)
Select the language to be used in the display:
11.3.3 Units (2/16)
Select the units to be used in the display:
• SI: m, kW, bar...
• US: ft, HP, psi...
11.3.4 Pump family (3/16)
Select pump family according to the pump nameplate:
• CR, CRI, CRN, CRT
• SP, SP-G, SP-NE
•...
Select "Other" if the pump family is not on the list.
11.3.5 Rated motor power (4/16)
Set the rated motor power, P2, according to the motor nameplate:
• 0.75 - 125 Hp (0.55 - 90 kW).
The setting range is size-related, and the factory setting
corresponds to the rated power of the CUE.
Check that equipment connected is ready for
start-up, and that the CUE has been connected to
the power supply.
Have nameplate data for motor, pump and CUE at
hand.