English (US)
24
11.3.20 Manual setting when the direction of rotation is not
visible (13/16)
It must be possible to observe the head or flow rate.
Information displays.
• Press [OK] to continue.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
The first test is completed.
• Write down the pressure and/or flow rate, and press OK to
continue the manual test with the opposite direction of
rotation.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
The second test is completed.
Write down the pressure and/or flow rate, and state which test
gave the highest pump performance:
• First test
• Second test
• Perform new test.
The correct direction of rotation has now been set.
• Press [OK] to set the setpoint. See section 11.3.17 Setpoint
(15/16).
11.4 GENERAL
The menu makes it possible to return to the start-up guide, which
is usually only used during the first start-up of the CUE.
11.4.1 Return to start-up guide (0.1)
State your choice:
•Yes
•No.
If "Yes" is selected, all settings will be erased, and the entire
start-up guide must be completed.
If the start-up guide is started, all previous
settings will be erased!
The start-up guide must be carried out on a cold
motor!
Repeating the start-up guide may lead to heating
of the motor.