EasyManuals Logo
Home>Grundfos>Water Pump>Hydro Multi-E Series

Grundfos Hydro Multi-E Series User Manual

Grundfos Hydro Multi-E Series
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
English (GB)
17
10.1.1 Setpoint setting
Set the desired setpoint by pressing or . The setpoint can
be set on any of the pumps in the system and applies to the
complete booster system.
The light fields on the control panel will indicate the setpoint set.
Pump in constant-pressure control mode
Hydro Multi-E systems are as standard set up from factory as
pressure boosting systems, but can be set up to other control
modes. See CRI and CRIE IO installation and operating
instructions. The following example applies to a pump in an
application where a pressure sensor gives a feedback to the
pump. If the sensor is retrofitted to the pump, it must be set
manually as the pump does not automatically register a
connected sensor.
Figure 29 shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 3 bar with a sensor measuring
range from 0 to 6 bar. The setting range is equal to the sensor
measuring range.
Fig. 29 Setpoint set to 3 bar, constant-pressure control mode
Fig. 30 Constant pressure curve
Setting to maximum curve:
Press
continuously to change over to the maximum curve
of the pump (top light field flashes). When the top light field is
on, press and hold for
for 3 seconds until the light field
starts flashing.
To change back, press
continuously until the desired
setpoint is indicated.
Example: Pump set to maximum curve.
Figure 31 shows that the top light field is flashing, indicating
maximum curve.
Fig. 31 Maximum curve duty
Setting to minimum curve:
Press
continuously to change over to the minimum curve
of the pump (bottom light field flashes). When the bottom light
field is on, press and hold
for 3 seconds until the light field
starts flashing.
To change back, press continuously until the desired
setpoint is indicated.
Example: Pump set to minimum curve.
Figure 32 shows that the bottom light field is flashing, indicating
minimum curve.
Fig. 32 Minimum curve duty
TM05 4894 3512TM05 7901 35122
0
6
3
bar
H
Q
TM05 4896 2812TM05 4897 2812
H
Q
H
Q

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos Hydro Multi-E Series and is the answer not in the manual?

Grundfos Hydro Multi-E Series Specifications

General IconGeneral
BrandGrundfos
ModelHydro Multi-E Series
CategoryWater Pump
LanguageEnglish

Related product manuals