6. Test specifications
SQ / SQE 1
Type Stage
Flow
m3/h
Pressure
min. mvs
Pressure
nom. mvs
Pressure
max. mvs
Nom. effect
P1/115V
Amps
115V
Nom. effect
P1/230V
Amps
230V
SQ1-35
2
043 46 50
590 5.10 580 2.50
5-SQ-90 1 31 34 36
SQ1-50
3
065 70 76
810 7.00 780 3.30
5-SQ-140 1 48 53 56
SQ1-65
4
087 94 101
1050 9.00 1000 4.30
5-SQ-180 1 65 71 74
SQ1-80
5
0 110 118 127
1180 5.10
5-SQ-230 1 83 90 93
SQ1-95
6
0 132 142 153
1380 6.00
5-SQ-270 1 100 108 112
SQ1-110
7
0 154 166 178
1590 7.00
5-SQ-320 1 117 126 132
SQ1-125
8
0 176 190 204
1820 7.80
5-SQ-360 1 134 144 152
SQ1-140
9
0 198 214 229
2020 8.6
5-SQ-410 1 151 162 171
SQ1-155
10
0 221 238 255
2190 9.6
5-SQ-450 1 168 181 190
SQ / SQE 2
Type Stage
Flow
m3/h
Pressure
min. mvs
Pressure
nom. mvs
Pressure
max. mvs
Nom. effect
P1/115V
Amps
115V
Nom. effect
P1/230V
Amps
230V
SQ2-35
2
041 44 49
730 6.30 710 3.00
10-SQ-110 2 32 35 38
SQ2-55
3
062 68 74
1050 9.0 1000 4.30
10-SQ-160 2 50 54 59
SQ2-70
4
081 88 96
1270 5.50
10-SQ-200 2 66 71 78
SQ2-85
5
0 100 109 119
1550 6.80
10-SQ-240 2 81 88 96
SQ2-100
6
0 121 132 143
1860 8.00
10-SQ-290 2 100 108 118
SQ2-115
7
0 143 155 168
2110 9.30
10-SQ-330 2 119 128 139
Water temperature: 20-25
°C
Max. testtime: 5 min
To be tested at nominal voltage an frequence
Flow adjusted to +/- 0.02