www.gtec-power.de 66
3) Set the UPS parallel parameters through MTR software
Above is our MTR software, connect MTR SW to UPS, find the setting page, set as below.
• 2 UPS in parallel
The first UPS should be set as below.
System Mode: Parallel
United Number: 2
System ID: 0
The second UPS should be set as below.
System Mode: Parallel
United Number: 2
System ID: 1
• 3 UPS in parallel
The first UPS should be set as below.
System Mode: Parallel
United Number: 3
System ID: 0
The second UPS should be set as below.
System Mode: Parallel
United Number: 3
System ID: 1
The third UPS should be set as below.
System Mode: Parallel
United Number: 3
System ID: 2
Note: Keep the other parameters same for UPS in the parallel system.