Move & Installation
Keep the equipment away from heat source or air outlets.
In case of fire, use dry powder or gas extinguisher only, any liquid
extinguisher can result in electric shock.
Don’t start the system if any damage or abnormal parts founded.
Contacting the UPS with wet material or hands may be subject to electric
shock.
Use proper facilities to handle and install the UPS. Shielding shoes,
protective clithes and other protective facilities are necessary to aviod
injury.
During positioning, keep the UPS way from shock or vibration.
Install the UPS in proper environment, more detail in section 2.3.
Debug & Operate
Make sure the grounding cable is well connected before connecting the
power cables, the grounding cable and neutral cable must be in
accordance with the local and national codes practice.
Before moving or re-connecting the cables, make sure to cut off all the
input power sources, and wait for at least 10 minutes for internal
discharge. Use a multi-meter to measure the voltage on terminals and
ensure the voltage is lower than 36V before operation.
The earth leakage current of load will be carried by RCCB or RCD.
Initial check and inspection should be performed after long time storing
of UPS.
Maintenance & Replacement
All the equipment maintenance and servicing procedures involving
internal access need special tools and should be carried out only by
trained personnel. The components that can be accessed by opening the
protective cover with tools cannot be maintenance by user.
This UPS full complies with “IEC /EN62040-1 General and safety
requirements for use in operator access area UPS”. Dangerous voltages
are present within the battery area.
However, the risk of contact with these high voltages is minimized for
non-service personnel. Since the component with dangerous voltage can
only be touched by opening the protective cover with a tool, the
possibility of touching high voltage component is minimized. No risk
exists to any personnel when operating the equipment in the normal
manner, following the recommended operating procedures in this
manual.