EasyManua.ls Logo

Guspro BB-8416884 - Page 100

Default Icon
158 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66
Determining the PID Constants (AT or Manual Settings) Section 3-8
Auto-tuning will stop if the Run/Reset parameter is set to Reset and the
Reset Operation parameter is set to stop control, or if you switch to man-
ual operation.
The following operation will be performed if the Reset Operation parame-
ter is set to fixed SP operation.
If the Run/Reset parameter is changed to Reset during auto-tuning,
the present SP will be changed to the fixed SP or the remote SP after
autotuning has been completed.
If auto-tuning is executed while the Run/Reset parameter is set to Re-
set and the Run/Reset parameter is changed to Run during auto-tun-
ing execution, the program will be started after completing auto-tuning.
The results of AT are reflected in the Proportional Band (P), Integral Time
(I), and Derivative Time (D) parameters for the PID set at the time AT exe-
cution starts. For details on PID sets, refer to PID Sets on page 136.
AT Operations AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for
the AT Execute/Cancel parameter. During execution, the AT Execute/Cancel
parameter on the No. 1 display flashes. When AT ends, the AT Execute/Can-
cel parameter turns OFF, and the No. 1 display stops flashing.
If you move to the operation level during AT execution, the No. 2 display
flashes to indicate that AT is being executed.
Only the following parameters can be changed during auto-tuning: Communi-
cations Writing, Run/Reset, and AT Execute/Cancel. Other parameters cannot
be changed.
AT Calculated Gain
The AT Calculated Gain parameter sets the gain for when PID values are cal-
culated using AT. When emphasizing response, decrease the set value. When
emphasizing stability, increase the set value.
.i
233.0
C
.p
(0
.d
40.0
PID Setting Level
PID* Proportional Band
PID* Integral Time
PID* Derivative Time
(
: 1 to 8)
at
off
at
at-2
AT Execute/Cancel
No. 1 displa
y
100% AT execution in progress
C
25.0
100.0
C
25.0
100.0
PV/SP
AT execution in progress
No. 2 display

Table of Contents