REMOTE CONTROL 
55 
Parameter  0 
Output off at power up 
  OFF 
Output off at power up 
  1 
Output on at power up 
  ON 
Output on at power up 
Return Parameter  0 
Output off at power up 
  1 
Output on at power up 
SYSTem:COMMunicate:ENABle 
Set
Query
 
Description 
Enables/Disables LAN, GPIB or USB remote 
interfaces as well as remote services  (Sockets, Web 
Server).  
Syntax 
Query Syntax 
SYSTem:COMMunicate:ENABle <mode>,<interface> 
SYSTem:COMMunicate:ENABle? <interface> 
Parameter  <mode> 
 
  OFF 
Turns the selected mode off. 
  0 
Turns the selected mode off. 
  ON 
Turns the selected mode on. 
  1 
Turns the selected mode on. 
  <interface> 
 
  GPIB 
Select GPIB 
  USB 
Select USB 
  LAN 
Select LAN 
  SOCKets 
Select Sockets 
  WEB 
Select the web server 
Return Parameter  0 
The selected mode is off. 
  1 
The selected mode is on. 
Example SYST:COMM:ENAB 1,USB 
Turns the USB interface on. 
Query Example  SYST:COMM:ENAB? USB 
1 
Queries the USB state, returns 1 (USB is on).