28
ELECTRICAL SCHEMATIC
Models 1000 and 1250
Sheet 1 of 2
02
A
04
06
08
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
B C D E F G H J K L M N P Q
(12 AWG)
(10 AWG)
TB1-PE
40A
L1
L2
-Q00
L3
(12 AWG)
TB1-PE
TB1-3
TB1-2
TB1-1
L3-1A
L2-1A
L1-1A
L3-1
L2-1
L1-1
L1-5A
L3-5
L1-5
TB1-20
TB1-19
L1-3
L2-3
L3-3
L1-3A
L2-3A
L3-3A
TB1-7
TB1-9
TB1-11
TB1-PE
(12 AWG)
M
HEATER 1
70 W, 460VAC
0.15A
COMPRESSOR 1
460 VAC, 3 PH
6HP, 9.0 RLA
M
FAN 1
1.25 KW
460 VAC
1.9 FLA
7 - 10 AMP
(SET @ 9A)
17A
-F11
-K62
21 22
-K62
-K43
1.4 - 2 AMP
(SET @ 2A)
17A
-F13
**MOUNTED
ON -T22
-F22
-F22C
-F22B
-F22A
1A
1A
1A
FU22.1
5A
FU22
24V
120V
460V
400V
230V
208V
COM
FU22.2
N
PLEASE NOTE:
FOR OPERATION 380-400VAC/3PH/50HZ,
MOVE PRIMARY TO 400VAC TAP.
-T22
24/120 VAC SECONDARY
208/230/400/460 VAC PRIMARY
100VA
CONNECT TO BACKPANEL
TB2-1
ELECTRICAL SUPPLY
480VAC/3PH/60HZ/GND
SHT#2 4B
SHT#2 4N