20
Dryer Set Point Table
DIP Switch Settings
DIP Switch Description On Off
1 Evaporator Outlet Temperature Sensor Disabled Enabled
2 Status Menu Scrolling Disabled Enabled
3 Reserved N/A N/A
4 Reserved N/A N/A
Dryer Configuration
Description Units Lower Upper Increment Default
Service Interval Hours 0 9999 1 4000
Energy Cost Decimal 0.00 0.99 0.01 0.13
Total Hours Hours 0 999999 1 0
Proportional Gain Gain 0.0 100.0 0.1 3.0
Integral Time Seconds 0.0 200.0 0.1 100.0
Derivative Time Seconds 0.0 200.0 0.1 20.0
Set Value Celsius 0.0°C (32.0°F) 15.0°C (59.0°F) 0.1°C (0.2°F) 3.3°C (37.9°F)
Time On Minutes 0.0 10.0 0.1 3.0
Time Off Minutes 0.0 10.0 0.1 3.0
Modbus Device Address Integer 1 247 1 1
Full Load Power Watts 0 29999 10 0