18
PMEMP60DP
HBM A0623-6.1 en/de/fr
6.3.2 Outputs (from the PLC to MP55IBS)
Limit values
Limit values are displayed in the same format as the measured values (16 bit
integer, 32 bit integer or floating format). The operating direction and
hysteresis remain unchanged and are set via the operating panel or the
CANbus.
Control word
Bits Name Meaning
0 ZERO 01 autom. triggers zeroing
1 TAR 01 triggers taring
2 SHUNT SHUNT ON / OFF
3 res reserved
4 CLRMAX 01 clears the MAX peak value store
5 CLRMIN 01 clears the MIN peak value store
6 HOLDMAX 1: freeze MAX peak value store
7 HOLDMIN 1: freeze MIN peak value store
8 PAR1 parameter set selection bit 1
9 PAR2 parameter set selection bit 2
10..15 res reserved
Tab 6.7: Contents of control word