- 42 -
Service Call 0844 736 9138, Technical Help (Chargeable) Call 0906 802 0253
19.4.1 Pump (head only)
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Disconnect the electrical plug (22) from the main board.
Remove the four cap head screws (20).
Carefully remove the pump head (21) together with cable.
Do not strain cable.
Reconnect wiring to new pump head and  t cover.
Fit the new pump head by repeating the operations in
reverse.
19.4.2 Automatic air vent
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Remove the retaining clip (19).
Remove the automatic air vent (17).
Fit the new automatic air vent and ‘O’ ring ensuring the vent
cap is left loose.
Re ll, vent and pressurise the boiler.
19.4.3 Low water pressure sensor
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Disconnect the electrical lead (4).
Remove the retaining clip (6), remove the low water pressure
sensor (5).
Fit the new low water pressure sensor.
Re ll vent and pressurise the boiler.
19.4.4 Safety discharge valve
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Remove the low water pressure sensor as described in the
previous section.
Undo the safety discharge valve union and remove the pipe.
Disconnect the Central Heating isolation valve.
Remove the securing clips and withdraw the safety discharge
valve plastic housing (29).
Remove the safety discharge valve.
Fit new ‘O’ ring. Re ll, vent and pressurise the boiler.
19.4.5 Flow sensor and impeller
Remove the the electrical connection (12).
Unclip the  ow sensor (13).
Unscrew the impeller housing (28) and remove the impeller.
19.4.6 Bypass
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Remove the bypass valve retaining nut (26) to remove the
bypass from its housing (25).
After replacing the bypass, re ll, vent and pressurise the
boiler.
19.4.7 3 way valve motor and diverter valve
Drain the boiler heating circuit as described in the appropriate
chapter "Draining".
Disconnect the electrical plug (2).
Remove the retaining clip (3).
Remove the three way valve motor (1).
Remove the diverter valve retaining nut.
Remove the diverter valve.
Fit new three way valve motor and diverter valve assembly.
Re ll, vent and pressurise the boiler.
19.4.8 Plate-to-plate heat exchanger
Drain the boiler heating and domestic hot water circuits as
described in the appropriate chapter "Draining".
Remove the two securing screws (23).
Remove the plate-to-plate heat exchanger (16).
When replacing the plate-to-plate heat exchanger, ensure that
the four rubber sealing washers are  tted into the hydroblock.
NOTE: The plate-to-plate heat exchanger only  ts one way.
Re ll, vent and pressurise the boiler.