13 Error Handling
64 KRONOS 20
- Notify HEINZMANN.
3094 ErrIntern 3194 SErrIntern
Cause: - Internal programming or computing error, so-called "EXCEPTION" error.
Response: - Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action: - Write down the values of the parameters 3195 SExceptionNumber,
3196 SExceptionAddrLow, 3197 SExceptionAddrHigh and 3198 SExceptionFlag
- Restart governor by a reset
- Notify HEINZMANN.