14 Parameter Description
KRONOS 20 71
No. Name Signification
318 StepperPosDeadBand
Level: 4
Range: 0..3650 steps
Page(s):
Dead band for gas valve positioning. Prevents
continuous stepping
319 StepperPosSubst
Level: 4
Range: 0..3650 steps
Page(s):
Substitute value for valve position at occurence of fatal
errors.
Range depends on actual gas valve
810 FunctEngineStop
Level: 6
Range: -5..5
Page(s):
Switch assignment to function „Engine stop“.
Gas valve will be closed
828 FunctErrorReset
Level: 6
Range: -5..5
Page(s):
Switch assignment to function „Reset errors“
912 AssignIn_MnfldPress
Level: 6
Range: 0..5
Page(s):
Assignment of input channel to manifold pressure
913 AssignIn_MnfldTemp
Level: 6
Range: 0..5
Page(s):
Assignment of input channel to manifold temperature
914 AssignIn_MeasPower
Level: 6
Range: 0..5
Page(s):
Assignment of input channel to output power feedback
915 AssignIn_Lambda
Level: 6
Range: 0..5
Page(s):
Assignment of input channel to lambda signal feedback
916 AssignIn_CH4Content
Level: 6
Range: 0..5
Page(s):
Assignment of input channel to CH4 content feedback
986 MnfldPressSensorLow
Level: 4
Range: 0..5 bar
Page(s):
Min. value of manifold pressure sensor
987 MnfldPressSensorHigh
Level: 4
Range: 0..5 bar
Page(s):
Max. value of manifold pressure sensor