14 Parameter Description
KRONOS 20 73
No. Name Signification
1400 ClosedLpPowerMinRate
Level: 4
Range: 0..100 %
Page(s):
Output power switch point for mode change from Open
loop mode to Closed loop mode
1401 ClosedLoopGov:I
Level: 4
Range: 0..100 %
Page(s):
Stability value for lambda control in Closed loop mode
1410 EngineDisplacement
Level: 4
Range: 0..100 dm³
Page(s):
Engine Displacement
1411 EngineRatedPower
Level: 4
Range: 0..2500 kW
Page(s):
Engine rated power
1412 VolEfficiencyConst
Level: 4
Range: 0,5..1
Page(s):
Constant value for volumetric efficiency of the engine
1413 MechEfficiencyConst
Level: 4
Range: 0,1..0,5
Page(s):
Constant value for mechanical efficiency of the engine
1420 ThroatArea
Level: 4
Range: 300..30000 mm²
Page(s):
Throat area of gas mixer insert
1421 GasMeteringHolesArea
Level: 4
Range: 100..10000 mm²
Page(s):
Overall area of gas holes in the gas mixer insert
1422 RefMeteringHolesArea
Level: 4
Range: 100..10000 mm²
Page(s):
Overall area of reference gas holes in the gas mixer
insert. Normally the same as in 1421
1423 HolesCorrFactor
Level: 4
Range: 1..2
Page(s):
Correction factor for geometry of gas holes (depends on
actual gas mixer insert)
1424 VenturiEfficiency
Level: 4
Range: 0,5..1
Page(s):
Correction factor for efficiency of gas mixer insert ho-
les (depends on actual gas mixer insert)