Fault reports and their correction
10
Betriebsanleitung_firestar_18-40_Lambda_Englisch_V1.6 29
Other possible faults
Cause
Corrective actions
Short burning time
Incorrect or fuel with too low
calorific value (e.g. softwood)
Use required fuel or
hardwood
The feed pressure (flue draft) is
too high.
Call for service
Boiler pulsates
Too much fuel gas, which cannot
be burned and removed
Check fuel dimensions
Call for service
Incorrect air intake
Check the tightness of the
test openings and doors
In case of leakage, call for
service
Too long loading of the buffer
The boiler capacity is for the
application too small.
Call for service
The hydraulic system is faulty.
Call for service
The heating behaviour is faulty.
Adjust the heating behaviour
to the heat demand
Excessively condensate is
formed in the chimney.
The chimney insulation is
insufficient.
Call for service
The exhaust gas collector or the
exhaust system is leaking.
Check test openings and
exhaust ports and if
necessary seal them
Cracks in the firebricks
The components contain a certain
amount of residual moisture.
(Note: Minor edge abrasion,
surface abrasion, crack formation
etc. does not lead to malfunction
and therefore does not constitute
a warranty)
For wide cracks or broken
out pieces, which extend to
the boiler construction: Call
for service