7 Software for HIMatrix Systems HIMatrix
Page 42 of 72 HI 800 023 E Rev. 1.01
7.4 Resource Parameters
DANGER
Physical injury possible due to incorrect configuration!
Neither the programming system nor the controller can verify certain project-specific
parameters. For this reason, enter these parameters correctly and verify the whole
entry.
These parameters are:
 System ID
 Rack ID, refer to the system manuals (HI 800 141 and HI 800 191).
 Safety Time
 Watchdog Time
 Main Enable
 Autostart
 Start Allowed
 Load allowed
 Reload Allowed
 Global Forcing Allowed
The following parameters are defined in the programming tool for the operations
permissible in the safety-related operation of the automation device and are referred to as
safety-related parameters.
Parameters that may be defined for safety-related operation are not firmly bound to any
specific requirement classes. Instead, each of these must be agreed upon together with the
responsible test authority for each separate implementation of the controller.
7.4.1 Parameters - Versions Beyond 7
In versions beyond 7, the distinction between system parameter of the resource and
system parameters of the hardware is made.
System Parameters of the Resource
These parameters define how the controller behaves during operation and are configured
for the resource in the Properties dialog box in SILworX.

Table of Contents

Other manuals for HIMA HIMatrix Series

Related product manuals