8 Safety-related Aspects of the User Program HIMatrix
Page 50 of 72 HI 800 023 E Rev. 1.01
Parameter /
Switch
Description
Default
value
Setting for safe
operation
Sum of UP Max.
Duration for Each
Cycle [µs]
Sum of the values indicated for Max. Duration for each
Cycle [µs] in all the user programs.
Not changeable
-
Target Cycle
Time Mode
Not applicable for HIMatrix controllers! Fixed -
Minimum configu-
ration version
Not applicable for HIMatrix controllers!
(it always corresponds to SILworX version 2, irrespec-
tive of the setting)
SILworX
V2
-
1)
200 ms with controllers, 100 ms with remote I/Os.
Table 27: System Parameters of the Resource - Versions Beyond 7