Installation RSPE30/32/35/37
Release
16
04/2019
57
Climatic
conditions
during
operation
Minimum clearance around
the device
Top and bottom device side: 3.94 in (10 cm)
Left and right device side: 0.79 in (2 cm)
Derating
b
:
3 K at the following clearance:
Top and bottom device side: 0.79 in (2 cm)
Left and right device side: 0 in (0 cm)
Ambient air temperature
c
Devices with operating temperature
characteristic value S (standard):
+32 °F ... +140 °F (0 °C ... +60 °C)
d
Devices with operating temperature
characteristic value E and T (extended):
RSPE32, RSPE37:
−40 °F ... +158 °F (−40 °C ... +70 °C)
e,f
−40 °F ... +185 °F (−40 °C ... +85 °C) for 16
hours (tested in accordance with
IEC 60068-2-2)
d,g
RSPE30, RSPE35:
−40 °F ... +158 °F (−40 °C ... +70 °C)
d
−40 °F ... +185 °F (−40 °C ... +85 °C) for 16
hours (tested in accordance with
IEC 60068-2-2)
d
Maximum inner temperature of
device (guideline)
Devices with operating temperature
characteristic value S (standard):
190°F (88°C)
Devices with operating temperature
characteristic value E and T (extended):
208°F (98°C)
Humidity 5 % ... 95 % (non-condensing)
Air pressure min. 700 hPa (+9842 ft; +3000 m)
max. 1060 hPa (-1312 ft; -400 m)