Chapter 5 Configuration of Communication parameters
5.2.5 Access to EH-ETH2 Configurator
When PLC is power on, STS LED turns on or blinks. You can access EH-ETH2 Configurator at both
conditions. We recommend setup the I/O assignment on CPU at first.
In the case that it is done with I/O correctly illumination
In the case that it is not done with I/O assignment blinking 0.25s
STS
RX1
RX2
OP4
POW
TX1
TX2
OP3
EH-ETH2
ETHERNET
WDE
TSK
OP1
OP5
ERR
IER
OP2
OP6
Figure 5.4 STS LED condition
Caution
- You can access EH-ETH2 Configurator without I/O assignment, but you can not use on-line connection of LADDER
EDITOR for Windows or Control Editor via Ethernet, and ASR connection data transmission without I/O assignment.
Open the “Communication Setting” window from [Option] menu in the initial screen (
Figure 5.5), set
destination IP address to connect to EH-ETH2.
For instance, in the case of the temporary IP address is "192.168.0.1", input “192.168.0.1” into IP address
field (
Figure 5.6). Port No. is fixed to “65535”.
Figure 5.5 The initial screen of EH-ETH2 Configurator
Figure 5.6 Communication Setting window
5-6