Chapter 5 Configuration of Communication parameters
Chapter 5 Configuration of communication
parameters
Communication parameters consist of Ethernet parameters and ASR parameters.
5.1 Ethernet parameters
It is required to configure the Ethernet parameters to this module before to start communication. The
Ethernet parameters are saved by the retained memory of this module as the part of setup file.
The detail of the Ethernet parameters is shown in
Table 5.1.
Table 5.1 Ethernet parameters
Items Default value
IP address of self station 192.168.0.1
Subnet mask of self station 255.255.255.0
Default gateway address 0.0.0.0
Transfer speed / type Auto Negotiation
Destination IP address 192.168.0.254
Send / Receive test
Logical port number 4000
Task Code Port Timeout Enable
Timeout value 30 s
Logical port number of self station 3004
Task code port 1
Type of service TCP/IP
Logical port number of self station 3005
Task code port 2
Type of service TCP/IP
Logical port number of self station 3006
Task code port 3
Type of service TCP/IP
Logical port number of self station 3007
For Task code
communication
usage
Task code port 4
Type of service TCP/IP
There are two ways to configure the Ethernet parameters.
(1) To configure using EH-ETH2 Configurator. (Recommend)
(2) To configure by the user program in CPU module.
In case of (1), it is required to change the position of dip switch into Configuration mode. In case of (2), it is
required to change the position of dip switch into Utility mode.
CAUTION
- It is possible to configure “Ethernet parameters” by EH-ETH2 Configurator or the user program. But the configuration
of “ASR parameters” can be done by only EH-ETH2 Configurator.
- The both parameters of not only “Ethernet parameters” but also “ASR parameters” are saved into setup file.
5-1