Figure 16 Service clearances for a three-rack, single-controller system
Table 19 Floor load rating and required clearances for a three-rack, single-
controller conguration
Floor load
rating (kg/m2)
Required clearance (a+b) m
c= -0.3 c=0 c=0.2 c=0.4 c=0.6 c=0.8 c=1.0 c=1.4
Over 700 0 0 0 0 0 0 0 0
600 0 0 0 0 0 0 0 0
500 0.5 0.2 0.1 0 0 0 0 0
Three-rack, single-controller conguration
Chapter 4: Site preparation specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 90