Settings can be altered or entered into the memory from the digital monitor without opening the start panel.
Function
7 segment display
Item Range
Precision/unit
Initial value
Multiple unit control
setting
F000 Control setting 0〜11 0
0: Single operation, 1: Multiple unit
control (communication supported)
Instantaneous power interrup-
tion (IPI) restart setting
※
F002
Instantaneous power inter-
ruption (IPI) setting
0〜11 00:ON、1:OFF
Remote operation
setting
F005
Remote control switch
method
0〜31 0
0:Panel setting, 1:Local fi xed,
2:Remote fi xed,
3: Remote switch signal
F006 Remote operation method 0〜11 00:Pulse input, 1:Level input
F007
Remote operation shut-
down recovery
0〜11 00:Disable, 1:Enable
AUTO setting F011 AUTO operation enable 0〜11 00:Enable, 1:Disable
Pressure setting switch
F018 Control pressure method 0〜21 00:Setting 1, 1:Setting 2, 2:Optional
Function setting
(optional)
F021 Pressure control mode 0〜21 0
0:Built-in sensor, 1:External contact,
2:External input
0.7/0.85MPa specifications
Pressure setting 1
※
F022 Target pressure 1 0.45〜0.85 0.01MPa 0.70
※ Setting can be altered at any time.
F023 Cutout pressure 1 0.47〜0.93 0.01MPa 0.78
F024 Cutin pressure 1 0.45〜0.85 0.01MPa 0.70
F025 Motor restart pressure 1 0.45〜0.85 0.01MPa 0.60
Pressure setting 2
※
F031 Target pressure 2 0.45〜0.85 0.01MPa 0.70
※ Setting can be altered at any time.
F032 Cutout pressure 2 0.47〜0.93 0.01MPa 0.78
F033 Cutin pressure 2 0.45〜0.85 0.01MPa 0.70
F034 Motor restart pressure 2 0.45〜0.85 0.01MPa 0.60
Shutdown history clear
F041(*1) History clear 0 〜11 00:Enter, 1:History clear
Note: ※ Setting can be altered at any time other than this.
*1 : If set to “1,” history is cleared. After clearing, it is automatically reset to “0”.
Do not alter settings for any F items not given in the table.
1. Cutout pressure setting range is 0.47 to 0.85 Mpa. The minimum difference between cutout pressure and cutin pressure
and minimum difference between cutout pressure and motor restart pressure is 0.05 MPa each.
2.Function for switching to pressure setting 2 by external pressure change input is optional.
3.If F006: Remote operation method is 1: Level input, be careful of contents of important matters for 7.6.6.
IMPORTANT