Settings can be altered or entered into the memory from the digital monitor without opening the start panel.
Function
7 segment display
Item Range
Precision/unit
Initial value
Multiple unit control
setting
F000 Control setting 011 0
0 Single operation, 1: Multiple unit
control (communication supported)
Instantaneous power interrup-
tion (IPI) restart setting
F002
Instantaneous power inter-
ruption (IPI) setting
011 00ON1OFF
Remote operation
setting
F005
Remote control switch
method
031 0
0Panel setting, 1Local fi xed,
2Remote fi xed,
3 Remote switch signal
F006 Remote operation method 011 00Pulse input, 1Level input
F007
Remote operation shut-
down recovery
011 00Disable, 1Enable
AUTO setting F011 AUTO operation enable 011 00Enable, 1Disable
Pressure setting switch
F018 Control pressure method 021 00Setting 1, 1Setting 2, 2Optional
Function setting
(optional)
F021 Pressure control mode 021 0
0Built-in sensor, 1External contact,
2External input
0.7/0.85MPa specifications
Pressure setting 1
F022 Target pressure 1 0.450.85 0.01MPa 0.70
Setting can be altered at any time.
F023 Cutout pressure 1 0.470.93 0.01MPa 0.78
F024 Cutin pressure 1 0.450.85 0.01MPa 0.70
F025 Motor restart pressure 1 0.450.85 0.01MPa 0.60
Pressure setting 2
F031 Target pressure 2 0.450.85 0.01MPa 0.70
Setting can be altered at any time.
F032 Cutout pressure 2 0.470.93 0.01MPa 0.78
F033 Cutin pressure 2 0.450.85 0.01MPa 0.70
F034 Motor restart pressure 2 0.450.85 0.01MPa 0.60
Shutdown history clear
F041(*1 History clear 0 11 00Enter, 1History clear
Note: Setting can be altered at any time other than this.
    *1 : If set to “1,” history is cleared. After clearing, it is automatically reset to “0”.
    Do not alter settings for any F items not given in the table.
1 Cutout pressure setting range is 0.47 to 0.85 Mpa. The minimum difference between cutout pressure and cutin pressure
and minimum difference between cutout pressure and motor restart pressure is 0.05 MPa each.
2Function for switching to pressure setting 2 by external pressure change input is optional.
3If F006: Remote operation method is 1: Level input, be careful of contents of important matters for 7.6.6.
IMPORTANT
14
3. HOW TO OPERATE [How to Set Control Functions]