Item Unit OSP-55VAN OSP-75VAN
Operating gas
Air
Suction pressure
Ambient pressure
Suction temperature
0 to 40
PQ Wide
Mode
Function
Disabled
(Ratings)
Discharge pressure
MPa
0.7
Discharge air capacity
(1)
m
3
/min
10.0 13.2
Enabled
Discharge pressure
MPa
0.6 0.85 0.6 0.85
Discharge air capacity
(1)
m
3
/min
10.5 9.0 13.9 11.9
Working range of PQ wide mode function
MPa 0.6 to 0.85
Discharge temperature
Atomospheric temperature15
Main motor shaft power
kW 55 75
Main motor type
Permanent Magnet Synchronous Motor,
Totally Enclosed Fan Cooled
Main motor insulation class
F type
Fan motor output (rating) kW 1.5 2.2
Fan motor type
3-phase cage type induction, fully closed type
Fan motor insulation class
E type
Starter type
Soft start
Power supply voltage V 380400415 50Hz
Capacity control type
V-mode: CPCS (constant* pressure control system) motor speed
control * discharge pressure±0.01 MPa
(3)
I-mode: online/offline control with blowoff
P-mode: automatic motor stop/restart control
Motor speed control range % About 30 to 105
Lubricating oil
NEW
HI
SCREW OIL NEXT (genuine synthetic oil)
Lubricating oil filling amount L
26 36
Total weight kg 1,220 1,390
Size (Width×Depth×Height) mm 2,000×1,200×1,800
NOTE
1
Discharge air capacity is a converted value according to the suction condition of the compressor.
2
Discharge pressure indicates gauge pressure.
3
Discharge air temperature varies depending on ambient temperature, load ratio etc.
The interphase voltage unbalance ratio of the power supply shall be within 1 %.
If the unbalance factor of the input current exceeds 20 % during the rated load operation, install AC reactor to the input side for improvement
of power supply cooperation. (The AC reactor is NOT the scope of supply from HITACHI)
4
Applicable for the load ratio between 30 and 105 %.
5

When a unit operates at the pressure below the PQ wide mode range, size-UP may be required for separate dryer and/or filters. Contact
Hitachi authorized distributors.
6
The compressor is not equipped with an earth leakage breaker. The earth leakage breaker should be provided by the customer.
7
The appearance and specifi cations are subject to change without notifi cation.
8
Intake temperature upper limit is 40 for dustproof specifi cations and optional specifi cations.