Chapter 4 Explanation of Functions
4 - 62
4.2.58 Intelligent output terminal setting
You can assign the functions described below to the intelligent
output terminals [11] to [15] (C021 to C025) and the alarm relay
terminal (C026).
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal
is used for relay output.
You can select the a-contact or b-contact output for individual output terminals by using functions "C031" to
"C035" and "C036".
When "01" (3 bits) or "02" (4 bits) is specified for the alarm code output "C062" (see Section 4.2.65), the
alarm code output is assigned to output terminals 11 to 13 or output terminals 11 to 14 (AC0 to AC3),
respectively. Subsequently, the settings of "C021" to "C024" are invalidated.
Data Description Reference item Page
00 RUN: Running signal Running signal (RUN) 4-64
01 FA1: Constant-speed reached
Frequency-arrival signals 4-64
02 FA2: Set frequency overreached
03 OL: Overload notice advance signal (1) Overload restriction/overload notice advance signal 4-40
04 OD: Output deviation for PID control PID function 4-26
05 AL: Alarm signal Protective functions -
06 FA3: Set frequency reached Frequency-arrival signals 4-64
07 OTQ: Over-torque Over-torque signal 4-67
08 IP: Instantaneous power failure
Instantaneous power failure/undervoltage 4-33
09 UV: Undervoltage
10 TRQ: Torque limited Torque limitation function 4-92
11 RNT: Operation time over Operation time over signal 4-66
12 ONT: Plug-in time over Plug-in time over signal 4-66
13 THM: Thermal alarm signal Electronic thermal protection 4-37
21 ZS: 0 Hz detection signal 0 Hz detection signal 4-66
24 FA4: Set frequency overreached 2
Frequency-arrival signals 4-64
25 FA5: Set frequency reached 2
26 OL2: Overload notice advance signal (2) Overload restriction/overload notice advance signal 4-40
27 Odc: Analog O disconnection detection
Window comparators function 4-74 28 OIDc: Analog OI disconnection detection
29 O2Dc: Analog O2 disconnection detection
31 FBV: PID feedback comparison PID function 4-26
32 NDc: Communication line disconnection RS485 4-67
33 LOG1: Logical operation result 1
Logical operation function 4-66
34 LOG2: Logical operation result 2
35 LOG3: Logical operation result 3
36 LOG4: Logical operation result 4
37 LOG5: Logical operation result 5
38 LOG6: Logical operation result 6
39 WAC: Capacitor life warning Capacitor life warning 4-70
40 WAF: Cooling-fan speed drop Cooling-fan speed drop 4-71
41 FR: Starting contact signal Starting contact signal 4-71
42 OHF: Heat sink overheat warning Heat sink overheat warning 4-71
43 LOC: Low-current indication signal Low-current indication signal 4-72
44 M01: General output 1
Easy sequence function -
45 M02: General output 2
46 M03: General output 6
47 M04: General output 4
48 M05: General output 5
49 M06: General output 6
50 IRDY: Inverter ready Inverter ready signal 4-72
51 FWR: Forward rotation Forward rotation signal 4-72
52 RVR: Reverse rotation Reverse rotation signal 4-73
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
Related code