Chapter 8 List of Data Settings
8 - 2
Code Function name Monitored data or setting Default
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
d025 User monitor 0 -2147483647 to 2147483647 (upper 4 digits including “-“)
− − −
4-5 d026 User monitor 1 -2147483647 to 2147483647 (upper 4 digits including “-“)
− − −
d027 User monitor 2 -2147483647 to 2147483647 (upper 4 digits including “-“)
− − −
d028 Pulse counter 0 to 2147483647 (upper 4 digits)
− − −
4-5
d080 Trip Counter 0. to 9999., 1000 to 6553 (10000 to 65530) (times)
− − −
4-5
d081 Trip monitoring 1
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
4-5
d082 Trip monitoring 2
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d083 Trip monitoring 3
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d084 Trip monitoring 4
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d085 Trip monitoring 5
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d086 Trip monitoring 6
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d090 Programming error monitoring Warning code
− − −
4-5
d102 DC voltage monitoring 0.0 to 999.9 (V)
− − −
4-5
d103 BRD load factor monitoring 0.0 to 100.0 (%)
− − −
4-6
d104
Electronic thermal overload
monitoring
0.0 to 100.0 (%)
− − −
4-6
8.3 Function Mode
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
_FF
F001 Output frequency setting
0.0, "start frequency" to "maximum frequency"
(or maximum frequency, 2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.00
{ {
4-7
F002 Acceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F202 Acceleration (1) time setting,
2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F302 Acceleration (1) time setting,
3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F003 Deceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F203 Deceleration time setting,
2nd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F303 Deceleration time setting,
3rd motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F004 Keypad Run key routing 00 (forward rotation), 01 (reverse rotation) 00
¯ ¯
4-7