Chapter 8 List of Data Settings
8 - 3
8.4 Extended Function Mode
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
_FF
Basic settings
A001 Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence), 10 (operation function result)
02
¯ ¯
4-8
A002 Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485),
04 (option 1), 05 (option 2)
02
¯ ¯
4-8
A003 Base frequency setting 30. to "maximum frequency " (Hz) 60.
¯ ¯
4-11
A203
Base frequency setting,
2nd motor
30. to "maximum frequency, 2nd motor" (Hz) 60.
¯ ¯
A303
Base frequency setting,
3rd motor
30. to "maximum frequency, 3rd motor" (Hz) 60.
¯ ¯
A004 Maximum frequency setting 30. to 400. (Hz) 60.
¯ ¯
4-11A204 Maximum frequency setting, 2nd motor 30. to 400. (Hz) 60.
¯ ¯
A304 Maximum frequency setting, 3rd motor 30. to 400. (Hz) 60.
¯ ¯
Analog input and others
A005 [AT] selection
00 (switching between O and OI terminals),
01 (switching between O and O2 terminals),
02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1),
04 (switching between O2 and keypad potentiometer) (*1)
00
¯ ¯
4-12
A006 [O2] selection
00 (single),
01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible),
03 (disabling O2 terminal)
03
¯ ¯
A011 [O]-[L] input active range start frequency 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
¯ {
4-14
A012 [O]-[L] input active range end frequency 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
¯ {
A013 [O]-[L] input active range start voltage 0. to "[O]-[L] input active range end voltage" (%) 0.
¯ {
A014 [O]-[L] input active range end voltage "[O]-[L] input active range start voltage" to 100. (%) 100.
¯ {
A015
[O]-[L] input active range start frequency
selection
00 (external start frequency), 01 (0 Hz) 01
¯ {
A016 External frequency filter time const. 1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis) 31.
¯ {
4-15
A017 Easy sequence function selection 00 (disabling), 01 (enabling) 00
¯ ¯
4-96
Multispeed operation and jogging
A019 Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals),
01 (bit: 8 speeds selectable with 7 terminals)
00
¯ ¯
4-47
A020 Multispeed frequency setting 0.0 or “start frequency” to “maximum frequency” (Hz) 0.00
{ {
A220 Multispeed frequency setting, 2nd motor 0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz) 0.00
{ {
A320 Multispeed frequency setting, 3rd motor 0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz) 0.00
{ {
A021 Multispeed 1 setting 0.0 or “start frequency” to “1st maximum frequency” (Hz) 0.00
{ {
A022 Multispeed 2 setting 0.0 or “start frequency” to “2nd maximum frequency” (Hz) 0.00
{ {
A023 Multispeed 3 setting 0.0 or “start frequency” to “3rd maximum frequency” (Hz) 0.00
{ {
A024 Multispeed 4 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A025 Multispeed 5 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A026 Multispeed 6 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A027 Multispeed 7 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A028 Multispeed 8 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A029 Multispeed 9 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A030 Multispeed 10 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A031 Multispeed 11 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A032 Multispeed 12 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A033 Multispeed 13 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A034 Multispeed 14 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A035 Multispeed 15 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A038 Jog frequency setting "Start frequency" to 9.99 (Hz) 1.00
{ {
4-50
A039 Jog stop mode
00 (free-running after jogging stops [disabled during operation]),
01 (deceleration and stop after jogging stops [disabled during operation]),
02 (DC braking after jogging stops [disabled during operation]),
03 (free-running after jogging stops [enabled during operation]),
04 (deceleration and stop after jogging stops [enabled during operation]),
05 (DC braking after jogging stops [enabled during operation])
00
¯ {
*1 This setting is valid only when the OPE-SR is connected.