Chapter 8 List of Data Settings
8 - 1
8.1 Precautions for Data Setting
The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable
the display of all parameters, specify "00" (full display) for the function code display restriction (b037).
To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock
mode selection (b031).
8.2 Monitoring Mode
With the default settings, the monitor always displays the data output according to the output frequency
monitoring (d001) after power-on. To change the initial display content, change the setting of the
initial-screen selection (b038) as required.
Code Function name Monitored data or setting Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
d001 Output frequency monitoring
0.00 to 99.99, 100.0 to 400.0 (Hz)
−
{ {
4-1
d002 Output current monitoring
0.0 to 999.9, 1000 to 9999 (A)
− − −
4-1
d003 Rotation direction minitoring
F (forward rotation), o (stopped), r (reverse rotation)
− − −
4-1
d004
Process variable (PV), PID
feedback monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), ⎡100 to ⎡999 (100000 to 999000)
− − −
4-1
d005
Intelligent input terminal
status
(Example)
Terminals FW, 7, 2, and 1: ON
Terminals 8, 6, 5, 4, and 3: OFF
− − −
4-2
d006
Intelligent output terminal
status
(Example)
Terminals 12 and 11: ON
Terminals AL, 15, 14, and 13: OFF
− − −
4-2
d007
Scaled output frequency
monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
−
{ {
4-2
d012 Torque monitoring
-200. to +200. (%)
− − −
4-3
d013 Output voltage monitoring
0.0 to 600.0 (V)
− − −
4-3
d014 Power monitoring
0.0 to 999.9 (kW)
− − −
4-3
d015 Cumulative power monitoring
0.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), ⎡100 to ⎡999 (100000 to 999000)
− − −
4-3
d016
Cumulative operation RUN
time monitoring
0. to 9999., 1000 to 9999 (10000 to 99990), ⎡100 to ⎡999 (100000 to 999000) (hr)
− − −
4-3
d017
Cumulative power-on time
monitoring
0. to 9999., 1000 to 9999 (10000 to 99990), ⎡100 to ⎡999 (100000 to 999000) (hr)
− − −
4-4
d018
Heat sink temperature
monitoring
-020. to 200.0 (°C)
− − −
4-4
d019
Motor temperature
monitoring
-020. to 200.0 (°C)
− − −
4-4
d022 Life-check monitoring
1: Capacitor on main circuit board
2: Cooling-fan speed drop
− − −
4-4
d023 Program counter
0 to 1024
− − −
4-4
d024 Program number monitoring
0000 to 9999
− − −
4-4
FW
8 7
6
5
4
3 2 1
AL 15 14 13 12 11
2 1
ON
OFF