Chapter 5 Error Codes
5 - 9
5.2 Warning Codes
The following table lists the warning codes and the contents of parameter readjustments:
Warning code Target function code Condition Basic function code
001/ 201 Frequency upper limit setting (A061/A261) >
Maximum frequency setting
(A004/A204/A304)
002/ 202 Frequency lower limit setting (A062/A262) >
004/ 204/ 304 Base frequency setting (A003/A203/A303) (*1) >
005/ 205/ 305
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
>
006/ 206/ 306 Multispeed 1 to 15 settings (A021 to A035) >
009 Home search speed setting (P015) >
012/ 212 Fequency lower limit setting (A062/A262) >
Frequency upper limit setting
(A061/A261)
015/ 215 Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
>
016/ 216 Multispeed 1 to 15 settings (A021 to A035) >
019
Frequency upper limit setting (A061/A261)
<
Home search speed setting
(P015)
021/ 221 <
Fequency lower limit setting
(A062/A262)
025/ 225 Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
<
031/ 231 Frequency upper limit setting (A061/A261) <
Start frequency adjustment (b082)
032/ 232 Fequency lower limit setting (A062/A262) <
035/ 235/ 335 Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
<
036 Multispeed 1 to 15 settings (A021 to A035) <
037 Jog frequency setting (A038) <
085/ 285/ 385
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
<>
Jump (center) frequency settings
1/2/3 ± " Jump (hysteresis)
frequency width settings 1/2/3"
A063 ± A064, A065 ± A066,
A067 ± A068 (*3)
086 Multispeed 1 to 15 settings (A021 to A035) <>
091/ 291 Frequency upper limit setting (A061/A261) >
Free-setting V/f frequency (7)
(b112)
092/ 292 Fequency lower limit setting (A062/A262) >
095/ 295 Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
>
096 Multispeed 1 to 15 settings (A021 to A035) >
110
Free-setting V/f frequency (1) to (6) (b100, b102, b104, b106,
b108, b110)
>
Free-setting V/f frequency (2) to (6) (b102, b104, b106, b108,
b110)
<
Free-setting V/f frequency (1)
(b100)
Free-setting V/f frequency (1) (b100) >
Free-setting V/f frequency (2)
(b102)
Free-setting V/f frequency (3) to (6) (b104, b106, b108, b110) <
Free-setting V/f frequency (1) (2) (b100, b102) >
Free-setting V/f frequency (3)
(b104)
Free-setting V/f frequency (4) to (6) (b106, b108, b110) <
Free-setting V/f frequency (1) to (3) (b100, b102, b104, b110) >
Free-setting V/f frequency (4)
(b106)
Free-setting V/f frequency (5) (6) (b108, b110) <
Free-setting V/f frequency (1) to (4) (b100, b102, b104, b106) >
Free-setting V/f frequency (5)
(b108)
Free-setting V/f frequency (6) (b110) <
Free-setting V/f frequency (1) to (5) (b100, b102, b104, b106,
b108)
>
Free-setting V/f frequency (6)
(b110)
120
Free setting, electronic thermal frequency (2) (3) (b017/b019) <
Free setting, electronic thermal
frequency (1) (b015)
Free setting, electronic thermal frequency (1) (b015) >
Free setting, electronic thermal
frequency (2) (b017)
Free setting, electronic thermal frequency (3) (b019) <
Free setting, electronic thermal frequency (1) (2) (b015/b017) >
Free setting, electronic thermal
frequency (3) (b019)
The inverter displays a warning code when the data set as a target function code satisfies the condition (specified in
the Condition column) in relation to the data set as the corresponding basic function code.
Each parameter (target function code) is readjusted to the data set as the basic function code (by updating at the
inverter start-up).
*1 In this case, the base frequency is rewritten at parameter readjustment. If the base frequency is updated to an
inappropriate value, a motor burnout may result. Therefore, if the warning is displayed, change the current base
frequency data to an appropriate value.
*2 These parameters are checked, even when the digital operator (02) is not specified for the frequency source
setting (A001).
*3 The current value of the jump (center) frequency is updated to "'the current value of the jump frequency' - 'value of
the Jump (hysteresis) frequency width (minimum)'".