Chapter 4 Explanation of Functions 
 
4 - 86 
4.2.91 Offline auto-tuning function 
The offline auto-tuning function allows you to make the inverter 
automatically measure and set the motor constants that are 
required for the sensorless vector control, 0Hz-range sensorless 
vector control, and vector control with sensor. 
When using the inverter to perform the sensorless vector control, 
0Hz-range sensorless vector control, and vector control with sensor 
for a motor of which the motor constants are unknown, measure the 
motor constants with the offline tuning function. 
When "00" (Hitachi general-purpose motor data) is specified for the 
motor constant selection (H002/H202), the motor constants of   
Hitachi's general-purpose motors are set as defaults. When you drive a Hitachi's general-purpose motor 
with the inverter, you can usually obtain the desired motor characteristics without problems. (If you cannot 
obtain the desired characteristics, adjust the motor constant settings as described in Section 4.2.92 or 
4.2.93.) 
If you intend to use the online tuning function described later, be sure to perform offline auto-tuning 
beforehand. 
The offline auto-tuning function applies only to the 1st motor and 2nd motor controls. Do not apply this 
function to the 3rd motor control. 
The motor constant data corresponding to the date of one phase of γ connection at 50 Hz. 
You should use off-line auto-tuning first by using factory default settings as long as you can .   
(There are some unusable functions and settings when using off line auto-tuning. Please see the following 
notices in detail.) 
Item  Function code  Data or range of data  Description 
Auto-tuning Setting  H001 
00  Disabling the auto-tuning 
01 
Enabling the auto-tuning (without 
motor rotation) 
02 
Enabling the auto-tuning (with motor 
rotation) 
Motor data selection  H002/H202 
00  Hitachi general-purpose motor data 
01  Automatically tuned data 
02 
Automatically tuned data (online 
auto-tuning enabled) 
Motor capacity  H003/H203  0.2 to 90.0 (kW) <0.2 to 160(kW)>
Note)<>:applied for 90 to 160kW 
Motor poles setting  H004/H204  2, 4, 6, 8, or 10 (poles)   
Auto constant R1  H030/H230  0.000 to 65.53 (Ω)  
Auto constant R2  H031/H231 
0.000 to 65.53 (Ω) 
 
Auto constant L  H032/H232  0.00 to 655.3 (mH)   
Auto constant Io  H033/H233  0.00 to 655.3 (A)   
Auto constant J  H034/H234 
0.001 to 9999. (kgm
2
) 
 
Base frequency 
setting 
A003/A203 
30 to maximum frequency setting 
(Hz) 
 
DC braking enable  A051 
00  Disabling DC braking 
01  Enabling DC braking 
AVR voltage select  A082 
200, 215, 220, 230, or 240 
Selectable only for 200 V class 
models 
380, 400, 415, 440, 460, or 480 
Selectable only for 400 V class 
models 
When using this function, follow the instructions below. 
1)Adjust the settings of base frequency (A003) and AVR voltage select (A082) to the motor specifications. 
When motor voltage is other than the altanatives, set as ”motor voltage (A082) “ * ”outputr voltage gain 
(A045) “ = “motor rated voltage” Please set 00 (constant torque characteristic[VC]) to V/F control 
mode(A044), and do not set free V/F setting(02). If you set free V/F setting (A044), auto-tuning function 
does not work.(see note 6) 
2) This function can properly apply to only the motors in the maximum applicable capacity class of your 
inverter or one class lower than the capacity class of your inverter. If this function is used for motors with 
other capacities, correct constant data may not be obtained. (In such cases, the auto-tuning operation 
may not be completed. If the auto-tuning operation is not completed, press the STOP/RESET key. The 
operation will end with an error code displayed.) 
 
H001: Auto-tuning Setting 
H002/H202: Motor data selection, 1st motor 
H003/H203: Motor capacity, 1st motor 
H004/H204: Motor poles setting, 1st motor 
H030/H230: Auto constant R1, 1
st
 /2
nd
 motor 
H031/H231: Auto constant R2, 1
st
/2
nd
 motor 
H032/H232: Auto constant L, 1
st
/2
nd
 motor 
H033/H233: Auto constant Io, 1
st
/2
nd
 motor 
H034/H234: Auto constant J, 1
st
 /2
nd
 motor 
A003/A203: Base frequency setting 
A051: DC braking selection 
A082: AVR voltage select 
b046: Reverse run proctection enable 
Related code