Chapter 4 Explanation of Functions
4 - 120
(iii) Writing data to a specified coil [05h]
This function writes data to a specified coil
The following table shows the updating of the coil status.
Coil status
OFFON ONOFF
Updating data (upper digit) FFh 00h
Updating data (lower digit) 00h 00h
(Example)
When sending an operation command to the inverter at slave address "10":
To start the inverter operation, "03" must be set in parameter "A002". Coil 1 is used to turn on an operation
command.
If the function to write data to a coil cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."
(iv) Writing data to a specified register [06h]
This function writes data to a specified register.
(Example)
When setting "50 Hz" as the base frequency setting (A003) in the inverter at slave address "5":
Since register "1203h" to store the base frequency setting (A003) has a data resolution of 1 Hz, specify
"50" (0032h) as the updating data to set "50 Hz".
If the function to write data to a specified register cannot be executed normally, the inverter will return an
exception response. For details, see Item (viii), "Exception response."
Query
Field name Sample setting
(hexadecimal)
1 Slave address (*1) 0A
2 Function code 05
3 Starting coil numbe
r
(upper digit) (*2)
00
4 Starting coil numbe
r
(lower digit) (*2)
00
5 Updating data (upper digit) FF
6 Updating data (lo
w
er digit) 00
7 CRC-16 code (upper digit) 8D
8 CRC-16 code (lower digit) 41
*1 If this query is broadcasted, no inverter will return any
response.
*2 Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.
Response
Field name Sample setting
(hexadecimal)
1 Slave address 0A
2 Function code 05
3 Starting coil numbe
r
(upper
digit)
00
4 Starting coil numbe
r
(lower
digit)
00
5 Updating data (upper digit) FF
6 Updating data (lo
w
er digit) 00
7 CRC-16 code (upper digit) 8D
8 CRC-16 code (lower digit) 41
Query
Field name Sample setting
(hexadecimal)
1 Slave address (*1) 05
2 Function code 06
3 Starting registe
r
numbe
r
(upper digit) (*2)
12
4 Starting registe
r
numbe
r
(lower digit) (*2)
02
5 Updating data (upper digit) 00
6 Updating data (lo
w
er digit) 32
7 CRC-16 code (upper digit) AD
8 CRC-16 code (lower digit) 23
*1 If this query is broadcasted, no inverter will return any
response.
*2 Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.
Response
Field name Sample setting
(hexadecimal)
1 Slave address 05
2 Function code 06
3 Starting registe
r
numbe
r
(upper digit)
12
4 Starting registe
r
numbe
r
(lower digit)
02
5 Updating data (upper digit) 00
6 Updating data (lo
w
er digit) 32
7 CRC-16 code (upper digit) AD
8 CRC-16 code (lower digit) 23