Chapter 4 Explanation of Functions
4 - 134
Register
No.
Function name
Function
code
R/W Monitoring and setting items Data resolution
Register
No.
1301h Selection of restart mode b001 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration
and stopping with matching frequency), 4 (restarting
with active matching frequency)
-
1302h
Allowable unde
r
-voltage power
failure time
b002 R/W 3 to 250 0.1 [sec.]
1303h
Retry wait time before motor
restart
b003 R/W 3 to 1000 0.1 [sec.]
1304h
Instantaneous power
failure/under-voltage trip alarm
enable
b004 R/W
0 (disabling), 1 (enabling), 2 (disabling during
stopping and decelerating to stop)
-
1305h
Number of restarts on power
failure/unde
r
-voltage trip events
b005 R/W 0 (16 times), 1 (unlimited) -
1306h Phase loss detection enable b006 R/W 0 (disabling), 1 (enabling) -
1307h
Restart frequency threshold
b007 (high) R/W
0 to 40000
0.01 [Hz]
1308h b007 (low) R/W
1309h Selection of retry after tripping b008 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration
and stopping with matching frequency), 4 (restarting
with active matching frequency)
-
130Ah
Selection of retry count after
undervoltage
b009 R/W 0 (16 times), 1 (unlimited) -
130Bh
Selection of retry count after
overvoltage or overcurrent
b010 R/W 1 to 3 1 [time]
130Ch Retry wait time after tripping b011 R/W 3 to 1000 0.1 [sec.]
130Dh
Electronic thermal setting
(calculated within the inverter
from current output)
b012 R/W 200 to 1000 0.1 [%]
130Eh Electronic thermal characteristic b013 R/W
0 (reduced-torque characteristic), 1 (constant-torque
characteristic), 2 (free setting)
-
130Fh (Reserved) - - Inaccessible -
1310h
Free setting, electronic thermal
frequency (1)
b015 R/W 0 to 400 1 [Hz]
1311h
Free setting, electronic thermal
current (1)
b016 R/W 0 to Rated current 0.1 [A]
1312h
Free setting, electronic thermal
frequency (2)
b017 R/W 0 to 400 1 [Hz]
1313h
Free setting, electronic thermal
current (2)
b018 R/W 0 to Rated current 0.1 [A]
1314h
Free setting, electronic thermal
frequency (3)
b019 R/W 0 to 400 1 [Hz]
1315h
Free setting, electronic thermal
current (3)
b020 R/W 0 to Rated current 0.1 [A]
1316h
Overload restriction operation
mode
b021 R/W
0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])
-
1317h Overload restriction setting b022 R/W 200 to 1500 0.1 [%]
1318h
Deceleration rate at overload
restriction
b023 R/W 10 to 3000
0.01
[
sec.]
1319h
Overload restriction operation
mode (2)
b024 R/W
0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])
-
131Ah Overload restriction setting (2) b025 R/W 200 to 1500 0.1 [%]
131Bh
Deceleration rate at overload
restriction (2)
b026 R/W 10 to 3000
0.01
[sec.]
131Ch Overcurrent suppression enable b027 R/W 0 (disabling), 1 (enabling) -
131Dh
Active frequency matching scan
start frequency
b028 R/W 200 to 1500 0.1 [%]
131Eh
Active frequency matching,
scan-time constant
b029 R/W 10 to 3000
0.01
[sec.]
131Fh
Active frequency matching,
restart frequency select
b030 R/W
0 (frequency at the last shutoff), 1 (maximum
frequency), 2 (set frequency)
-
1320h Software lock mode selection b031 R/W
0 (disabling change of data other than "b031" when
SFT is on), 1 (disabling change of data other than
"b031" and frequency settings when SFT is on), 2
(disabling change of data other than "b031"), 3
(disabling change of data other than "b031" and
frequency settings), 10 (enabling data changes
during operation)
-
1322h (Reserved) - - Inaccessible -
1323h
Run/power-on warning time
b034 (high) R/W
0 to 65535 1 [10h]
1324h b034 (low) R/W