Chapter 4 Explanation of Functions
4 - 136
Register
No.
Function name
Function
code
R/W Monitoring and setting items Data resolution
Register
No.
1354h (Reserved) - - Inaccessible -
1355h Start frequency adjustment b082 R/W 10 to 999 0.01 [Hz]
1356h Carrier frequency setting b083 R/W 5 to 120 (5 to 80 :90 to 160kW) 0.1 [kHz]
1357h
Initialization mode (parameters
or trip history)
b084 R/W
0 (clearing the trip history), 1 (initializing the data), 2
(clearing the trip history and initializing the data)
-
1358h Country code for initialization b085 R/W 0 (Japan), 1 (EU), 2 (U.S.A.) -
1359h
Frequency scaling conversion
facto
r
b086 R/W 1 to 999 0.1
135Ah STOP key enable b087 R/W 0 (enabling), 1 (disabling), 2 (disabling only stop) -
135Bh Restart mode after FRS b088 R/W
0 (starting with 0 Hz), 1 (starting with matching
frequency), 2 (starting with active matching
frequency)
-
135Ch (Reserved) - - Inaccessible -
135Dh Dynamic braking usage ratio b090 R/W 0 to 1000 0.1 [%]
135Eh Stop mode selection b091 R/W 0 (deceleration until stop), 1 (free-run stop) -
135Fh Cooling fan control b092 R/W
0 (always operating the fan), 1 (operating the fan only
during inverter operation [including 5 minutes after
powe
r
-on and powe
r
-off])
-
1360h (Reserved) - - Inaccessible -
1361h (Reserved) - - Inaccessible -
1362h Dynamic braking control b095 R/W
0 (disabling), 1 (enabling [disabling while the motor is
stopped]), 2 (enabling [enabling also while the motor
is stopped])
-
1363h Dynamic braking activation level b096 R/W 330 to 380, 660 to 760 1. [V]
1364h (Reserved) - - Inaccessible -
1365h
Thermistor for thermal protection
control
b098 R/W
0 (disabling the thermistor), 1 (enabling the thermistor
with PTC), 2 (enabling the thermistor with NTC)
-
1366h Thermal protection level setting b099 R/W 0. to 9999. 1. [
Ω
]
1367h Free-setting V/f frequency (1) b100 R/W 0. to "free-setting V/f frequency (2)" 1 [Hz]
1368h Free-setting V/f voltage (1) b101 R/W 0. to 8000 0.1 [V]
1369h Free-setting V/f frequency (2) b102 R/W 0. to "free-setting V/f frequency (3)" 1 [Hz]
136Ah Free-setting V/f voltage (2) b103 R/W 0. to 8000 0.1 [V]
136Bh Free-setting V/f frequency (3) b104 R/W 0. to "free-setting V/f frequency (4)" 1 [Hz]
136Ch Free-setting V/f voltage (3) b105 R/W 0. to 8000 0.1 [V]
136Dh Free-setting V/f frequency (4) b106 R/W 0. to "free-setting V/f frequency (5)" 1 [Hz]
136Eh Free-setting V/f voltage (4) b107 R/W 0. to 8000 0.1 [V]
136Fh Free-setting V/f frequency (5) b108 R/W 0. to "free-setting V/f frequency (6)" 1 [Hz]
1370h Free-setting V/f voltage (5) b109 R/W 0. to 8000 0.1 [V]
1371h Free-setting V/f frequency (6) b110 R/W 0. to "free-setting V/f frequency (7)" 1 [Hz]
1372h Free-setting V/f voltage (6) b111 R/W 0. to 8000 0.1 [V]
1373h Free-setting V/f frequency (7) b112 R/W 0. to 400. 1 [Hz]
1374h Free-setting V/f voltage (7) b113 R/W 0. to 8000 0.1 [V]
1375h to
137Ah
(Reserved) - - Inaccessible -
1383h (Reserved) - - Inaccessible -
1384h (Reserved) - - Inaccessible -
1385h Overvoltage suppression enable b130 R/W
0 (disabling), 1 (enabling), 2 (enabling with
acceleration)
-
1386h Overvoltage suppression level b131 R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h
Acceleration and deceleration
rate at overvoltage suppression
b132 R/W 10 to 3000
0.01
[sec.]
1388h
Overvoltage suppression
propotional gain
b133 R/W 0 to 255 0.01
1389h
Overvoltage suppression Integral
time
b134 R/W 0 to 65535
0.001
[sec.]
1390h to
1400h
(Reserved) - - Inaccessible -