Chapter 4 Explanation of Functions
4 - 139
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
142Ah
Frequency arrival setting for accel.
C042 (high) R/W
0 to 40000 0.01 [Hz]
142Bh C042 (low) R/W
142Ch
Frequency arrival setting for decel.
C043 (high) R/W
0 to 40000 0.01 [Hz]
142Dh C043 (low) R/W
142Eh PID deviation level setting C044 R/W 0 to 1000 0.1 [%]
142Fh
Frequency arrival setting for
acceleration (2)
C045 (high) R/W
0 to 40000 0.01 [Hz]
1430h C045 (low) R/W
1431h
Frequency arrival setting for
deceleration (2)
C046 (high) R/W
0 to 40000 0.01 [Hz]
1432h C046 (low) R/W
1433h to
1437h
(Reserved) - - Inaccessible -
1438h Maximum PID feedback data C052 R/W 0 to 1000 0.1 [%]
1439h Minimum PID feedback data C053 R/W 0 to 1000 0.1 [%]
143Ah (Reserved) R/W -
143Bh
Over-torque (forward-driving) level
setting
C055 R/W 0 to 150 1 [%]
143Ch
Over-torque (reverse regenerating)
level setting
C056 R/W 0 to 150 1 [%]
143Dh
Over-torque (reverse driving) level
setting
C057 R/W 0 to 150 1 [%]
143Eh
Over-torque (forward regenerating)
level setting
C058 R/W 0 to 150 1 [%]
143Fh (Reserved) - - Inaccessible -
1440h (Reserved) - - Inaccessible -
1441h
Electronic thermal warning level
setting
C061 R/W 0 to 100 1 [%]
1442h Alarm code output C062 R/W 0 (disabling alarm output), 1 (3 bits), 2 (4 bits) -
1443h Zero speed detection level C063 R/W 0 to 10000 0.01 [Hz]
1444h Heat sink overheat warning level C064 R/W 0 to 200 1 []
1445h to
144Ah
(Reserved) - - Inaccessible -
144Bh Communication speed selection C071 R/W
2 (loopback test), 3 (2,400 bps), 4 (4,800 bps), 5
(9,600 bps), 6 (19,200 bps)
-
144Ch Node allocation C072 R/W 1. to 32. -
144Dh
Communication data length
selection
C073 R/W 7 (7 bits), 8 (8 bits) -
144Eh Communication parity selection C074 R/W 00 (no parity), 01 (even parity), 02 (odd parity) -
144Fh Communication stop bit selection C075 R/W 1 (1 bit), 2 (2 bits) -
1450h
Selection of the operation after
communication error
C076 R/W
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors), 3
(stopping the motor after free-running), 4
(decelerating and stopping the motor)
-
1451h Communication timeout limit C077 R/W 0 to 9999 0.01 [sec.]
1452h Communication wait time C078 R/W 0 to 1000 1 [msec.]
1453h Communication mode selection C079 R/W 0 (ASCII), 1 (Modbus-RTU) -
1454h (Reserved) - - Inaccessible -
1455h [O] input span calibration C081 R/W 0 to 65530 1
1456h [OI] input span calibration C082 R/W 0 to 65530 1
1457h [O2] input span calibration C083 R/W 0 to 65530 1
1458h (Reserved) - - Inaccessible -
1459h Thermistor input tuning C085 R/W 0 to 10000 0.1
145Ah to
145Eh
(Reserved) - - Inaccessible -
145Fh Debug mode enable C091 R 0/1 -
1460h to
1468h
(Reserved) - - Inaccessible -
1469h Up/Down memory mode selection C101 R/W
0 (not storing the frequency data), 1 (storing the
frequency data)
-
146Ah Reset mode selection C102 R/W
0 (resetting the trip when RS is on), 1 (resetting
the trip when RS is off), 2 (enabling resetting only
upon tripping [resetting when RS is on]),
3(resetting only trip)
-
146Bh Restart mode after reset C103 R/W
0 (starting with 0 Hz), 1 (starting with matching
frequency), 2 (restarting with active matching
frequency)
-
146Ch (Reserved) - - Inaccessible -
146Dh FM gain adjustment C105 R/W 50 to 200 1 [%]
146Eh AM gain adjustment C106 R/W 50 to 200 1 [%]
146Fh AMI gain adjustment C107 R/W 50 to 200 1 [%]