Chapter 4 Explanation of Functions
4 - 141
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
1501h Auto-tuning Setting H001 R/W
0 (disabling auto-tuning), 1 (auto-tuning without
rotation), 2 (auto-tuning with rotation)
-
1502h Motor data selection, 1st motor H002 R/W
0 (Hitachi standard data), 1 (auto-tuned data), 2
(auto-tuned data [with online auto-tuning
function])
-
1503h Motor capacity, 1st motor H003 R/W (*1) -
1504h Motor poles setting, 1st motor H004 R/W
0 (2 poles), 1 (4 poles), 2 (6 poles), 3 (8 poles),
4 (10 poles)
-
1505h
Motor speed constant, 1st motor
H005 (high) R/W
0 to 80000 0.001
1506h H005 (low) R/W
1507h
Motor stabilization constant, 1st
motor
H006 R/W 0 to 255 1
1508h to
1514h
(Reserved) - - Inaccessible -
1515h
Motor constant R1, 1st motor
H020 (high) R/W
1 to 65530 0.001 [Ω]
1516h H020 (low) R/W
1517h
Motor constant R2, 1st motor
H021 (high) R/W
1 to 65530 0.001 [Ω]
1518h H021 (low) R/W
1519h
Motor constant L, 1st motor
H022 (high) R/W
1 to 65530 0.01 [mH]
151Ah H022 (low) R/W
151Bh
Motor constant Io
H023 (high) R/W
1 to 65530 0.01 [A]
151Ch H023 (low) R/W
151Dh
Motor constant J
H024 (high) R/W
1 to 9999000 0.001
151Eh H024 (low) R/W
151Fh to
1523h
(Reserved) - - Inaccessible -
1524h
Auto constant R1, 1st motor
H030 (high) R/W
1 to 65530 0.001 [Ω]
1525h H030 (low) R/W
1526h
Auto constant R2, 1st motor
H031 (high) R/W
1 to 65530 0.001 [Ω]
1527h H031 (low) R/W
1528h
Auto constant L, 1st motor
H032 (high) R/W
1 to 65530 0.01 [mH]
1529h H032 (low) R/W
152Ah
Auto constant Io, 1st motor
H033 (high) R/W
1 to 65530 0.01 [A]
152Bh H033 (low) R/W
152Ch
Auto constant J, 1st motor
H034 (high) R/W
1 to 9999000 0.001
152Dh H034 (low) R/W
152Eh to
153Ch
(Reserved) - - Inaccessible -
153Dh PI proportional gain for 1st motor H050 R/W 0 to 10000 0.1 [%]
153Eh PI integral gain for 1st motor H051 R/W 0 to 10000 0.1 [%]
153Fh
P proportional gain setting for 1st
motor
H052 R/W 0 to 1000 0.01
1540h to
1546h
(Reserved) - - Inaccessible -
1549h to
1550h
(Reserved) - - Inaccessible -
1551h
Terminal selection PI proportional
gain setting
H070 R/W 0 to 10000 0.1 [%]
1552h
Terminal selection PI integral gain
setting
H071 R/W 0 to 10000 0.1 [%]
1553h
Terminal selection P proportional
gain setting
H072 R/W 0 to 1000 0.01
1554h Gain switching time H073 R/W 0 to 9999 1 [msec.]
1555h to
1600h
(Reserved) - - Inaccessible -