Safety Instructions
vii
11. Distribution fuse / circuit breaker size marking is included in the manual to indicate that the unit shall be
connected with a Listed inverse time circuit breaker, rated 600 V with the current ratings as shown in
the table below:
Model No. Fuse Size (Maximum A) Circuit Breaker (Maximum A)
Type Rating Type Rating
L700-110L J 60 A Inverse time 60 A
L700-150L J 100 A Inverse time 100 A
L700-185L J 100 A Inverse time 100 A
L700-220L J 100 A Inverse time 100 A
L700-300L J 125 A Inverse time 125 A
L700-370L J 175 A Inverse time 175 A
L700-450L J 225 A Inverse time 225 A
L700-550L J 250 A Inverse time 250 A
L700-750L J 300 A Inverse time 300 A
L700-110H J 30 A Inverse time 30 A
L700-150H J 40 A Inverse time 40 A
L700-185H J 50 A Inverse time 50 A
L700-220H J 50 A Inverse time 50 A
L700-300H J 75 A Inverse time 75 A
L700-370H J 80 A Inverse time 80 A
L700-450H J 100 A Inverse time 100 A
L700-550H J 125 A Inverse time 125 A
L700-750H J 150A Inverse time 150 A
L700-900H J 225 A Inverse time 225 A
L700-1100H J 225 A Inverse time 225 A
L700-1320H J 300 A Inverse time 300 A
L700-1600H J 350 A Inverse time 350 A
12. “Field wiring connection must be made by a UL Listed and CSA Certified ring lug terminal connector
sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by
the connector manufacturer.”