6. Optional functions
148
SMGB0079 rev.0 - 01/2013
6.1.2  Available optional signals
The outdoor units have the following signals that are described in the following table.
These signals are set up through the PCB of the outdoor unit.
RAS-(2-2.5)HVNP / RAS-3HVNC
Input signals
Ind. Input signal Application Port
0
No setting application No setting —
1
Fixing the heating mode
This signal allows to pre-x the operation mode, in this case the heating 
mode, independently of what the indoor unit requests. If the indoor units 
request the oposite mode than the outdoor unit, the compressor will not start. 
This is very useful to set up a unique operation mode.
CN1 and CN2
2
Fixing the cooling mode
This signal allows to pre-x the operation mode, in this case the cooling 
mode, independently of what the indoor unit requests. If the indoor units 
request the oposite mode than the outdoor unit, the compressor will not 
start. This is very useful for computer rooms where the cooling mode is xed 
throughout the year.
CN1 and CN2
3
Demand thermo OFF
This signal allows to stop the compressor if it reaches a certain power as well 
as to put the indoor unit in Thermo-OFF. This is very useful for installations 
with high power consumption.
CN1 and CN2
4
Forced stoppage
This signal allows to control the stoppage of the compressor and the fans of 
the indoor as well as outdoor units. This is very useful when used with the 
alarm signals of the re prevention systems.
CN1 and CN2
5
Current control demand 60%
This signal allows to regulate current consumption and establish an average 
consumption of 60% of the rate point. This is very useful for installations that 
run 24 hours a day.
CN1 and CN2
6
Current control demand 80%
This signal allows to regulate current consumption and establish an average 
consumption of 80% of the rate point.This is very useful for installations that 
run 24 hours a day.
CN1 and CN2
7
Current control demand 100%
This signal allows to regulate current consumption and establish an average 
consumption of 100% of the rate point. This is very useful for installations 
that run 24 hours a day.
CN1 and CN2
Output signals
Ind. Output signal Application Port
0
No setting application No setting —
01
Operation signal
This signal allows to pick up the machine’s operation signal. This is very 
useful to start up additional systems such as humidiers, fans and other ad-
ditional air-conditioning systems.
CN7
02
Alarm signal
This signal picks up the machine’s alarm. This is very useful to warn that an 
alarm has been tripped.
CN7
03
Compressor ON signal
This single allows to pick up the compressor’s operation signal. It is very 
useful for checking signals during remote-control operation and for the 
interlock of the outdoor unit.
CN7
04
Defrost operation signal
This signal allows to pick up the defrosting of the unit. This is very useful to 
know how the indoor unit is operating if there is an abnormal situation.
CN7
  N O T E
Donotsetsamefunctiontomultipleinputport.Ifset,thehigherinputterminalnumberwillbecancelled.