8. Troubleshooting
185
SMGB0079 rev.0 - 01/2013
8
8.1.2  Failure of the power supply to the indoor unit and the remote control switch
•  The LED and the LCD are not indicated.
•  Not operated
If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action.
Phenomenon Cause Check item
Action 
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means of  
the voltmeter
Supply the power
Blown out fuse or activation of  the 
breaker at the power source
Short circuit supplied between  the 
wires
Check for any uncovered part of  
the wires
Remove the cause of the short  
circuit and replace the fuse
Short circuit of the wires to earth Measure the insulation  resistance
Remove the cause of the short  
circuit and replace the fuse
Failure of indoor unit fan motor
Measure resistance between  
wires and insulation resistance
Replace the fan motor and fuse
Blown out fuse at the control  cir-
cuit
Short circuit supplied between  the 
wires
Check for any uncovered part of  
the wires 
Remove the cause of the short  
circuit and replace the fuse 
Short circuit of the control circuit  
to earth
Measure the insulation  resistance
Remove the cause of the short  
circuit and replace the fuse 
Failure of indoor unit fan motor Measure the insulation  resistance
Remove the cause of the short  
circuit and replace the fuse
Failure of the transformer at the indoor unit side
Measure the voltage at the  sec-
ondary side
Replace the transformer
Disconnected cable of the remote control switch Connect the cable
Replace the cable or repair the  
cable
Insufcient contacting at the  con-
nectors of the remote control  
switch
Insufcient connection or  incorrect 
connection of the indoor  unit PCB
Check the connectors Correctly connect the connector
Insufcient connection  or incorrect 
connection of the  indoor unit PCB 
in the remote  control switch
Failure of the remote control switch
Check the remote control switch  
by means of the self-check mode  
*1)
Replace the remote control  switch 
if it failed
Failure of PCB
Unconnected wires to PCB Check the connectors Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check  mode *2)
Replace PCB if it failed
Incorrect wiring connection Take action according to the procedure that is displayed in  “TEST RUN”
N O T E
•  *1):RefertosectionSelf-checkingoftheremotecontrolswitch.
•  *2):RefertosectionSelf-checkingprocedureofPCBbymeansoftheRemoteControlSwitch.